Comment by taneq

11 hours ago

Yep, might be there was a known issue that was addressed, at which put in a new one. But just replacing a fuse (or, simultaneously worse and better, just resetting a breaker) without further investigation is just kicking a very spicy can down the road.

I had a doozy of a trip issue on one project, a motor would occasionally (not always, no real pattern, hot/cold/etc. didn’t matter) trip the breaker, requiring a sparky to come out and open up the panel to reset it. We tried a bunch of things, megger-ing the motor, testing peak startup current on each phase with a fancy meter, checking phase-to-neutral current (Larger than you’d think! But this was normal, apparently.)

Everything was normal. In the end all we could think something was weird about the contactor. They took it out (I was off site at the time) and took it down to the substation to test it out.

With three phases connected to the contactor (and nothing connected on the other side) they energised the coil, and with an almighty bang it tripped the main incomer and took the entire sub offline.

Turns out there was a manufacturing defect in the contactor and sometimes for a millisecond, if the phase of the moon was right, it dead shorted two phases.

So there, even when you know everything, you don’t know everything.