Definitely use quality surge protectors on expensive equipment connected to generators.

PSA: UPSes and GFCI/GFI extension cords won't work properly when connected to a stand-alone generator with a bonded neutral. I've tried using enterprise UPSes on such generators, but they absolutely won't work. In such scenarios, debond the generator's ground from neutral, apply a very large warning label to it being debonded, and drive a massive ground rod electrode into the ground as close to the generator as possible and ground the neutral there. This does work and is much safer because there's a stable voltage reference source. It's more of a hassle but can be necessary for some off grid and temporary scenarios.

> In such scenarios, debond the generator's ground from neutral

eeeeep. Please for the love of all that is holy, CONTACT AN ELECTRICIAN before messing around with that - or before creating a ground bond where none should be (i.e. TT grid [1]). You may end up endangering yourself if you do not exactly know what you are doing - in the case of TT, you get ground potential difference current from other parts of the grid flowing to ground via your generator's bond.

Also, take great care if your grounding is provided via municipal water service, or if your original grounding rod has dried out to the point it's ineffective.

Let me repeat: LET ELECTRICIANS DEAL WITH GROUNDING AND SURGE PROTECTION. Floating grounds and improper ground connections CAN BE LETHAL OR POSE A SERIOUS FIRE RISK.

AND YES THAT INCLUDES "ISLAND" SCENARIOS OR EMERGENCY POWER INPUTS (e.g. via CEE plugs and transfer switches).