Comment by michaelt
11 hours ago
I once worked at a company that had a wealth of backups. A backup generator, backup batteries as the generator takes a few seconds to start, a contract for emergency fuel deliveries, a complete failover data centre full of hot standby hardware, 24/7 ops presence, UPSes on the ops PCs just in case, weekly checks that the generators start, quarterly checks by turning off the breakers to the data centre, and so on.
It wasn't until a real incident that we learned: (a) the system wasn't resilient to the utility power going on-off-on-off-on-off as each 'off' drained the batteries while the generator started, and each 'on' made the generator shut down again; (b) the ops PCs were on UPSes but their monitors weren't (C13 vs C5 power connector) and (c) the generator couldn't be refuelled while running.
Even if you've got backup systems and you test them - you can never be 100% sure.
A plan that has never been executed is really just hope and wishful thinking.