Comment by VLM

5 hours ago

I find it interesting the discussion here is entirely about water temperature whereas the shutdown is entirely about NPSH.

True there is a small different in NPSH pump limit of hot summer water vs cold winter water, but not as much as you'd think.

Its not that the intake pipes are hanging out in the breeze above water; most pumps are designed not to cavitate at a certain input pressure (often pretty low) and I was bored enough to look it up and when the river is 134 cm below reference at this site, the pumps will be very unhappy long term if you keep sucking water in. They'll keep running, at a reduced rate, but cavitation will cause serious issues. At some sites, perhaps not this site, filtration systems (grates and stuff) on the input are designed for a certain ideal pressure and ideal flow rate, so that can also be a problem.

Thermal limits are also very arbitrary and designed to a financial limit. Most plants worldwide are limited to a delta V, I suppose there could exist an environmental law that limits to an arbitrary fixed temp. Normally if 10 gallons/sec heats up 10 degrees, then 100 gallons/sec would only heat 1 degree. But it would cost 10x as much and only be needed a couple days/year in the driest summers, so a tradeoff point, well chosen or not, was selected. Most absolute limits are utterly ridiculous like 90F. The only long term way to maintain a river at or above 90F is an air dew point of 90F and most people will be dead by then. I find it improbable the water temp is too high, everyone without air conditioning would already be dead if the dew point were substantially over 90F. You could probably "cook" a small lake or dam area with a nuclear plant into something like a giant hot tub, but not a free flowing river.

Looking at the mass media coverage, its mostly pictures and discussion of low water levels (the true cause) followed by journalist and consumer discussion about water temps, there is no meeting of the minds between the engineers and the general public and AI and journalists.

If for whatever weird reason, river levels were low in the winter, low NPSH at the pumps would shut it down just as effectively at a water temperature of 1 C. Large industrial water pumps react extremely poorly to low input pressure.