Comment by jermaustin1
10 hours ago
That's why they said "depending on country"
In North America we are on 120V, making a standard 15A outlet only 1500W max, and something like 1200W sustained. To use higher wattage appliances, we have to upgrade our outlets to 20A (2000/1600W) or up our voltage to 240V, but that carries a different set of plugs and outlets as well.
Usually the home service is 200+ amps these days which is 24 KW total across all circuits, though you're right that most individual circuits are only 10-15 amp.
> In North America we are on 120V, making a standard 15A outlet only 1500W max, and something like 1200W sustained.
It's 1800W for short periods and 1500W sustained.
1,800 watt for periods less then 3 hours and 1,440 watts for continuous loads over 3 hours.
Realistically, a 15A breaker won’t trip on a 2,300 watt load for at least a few minutes, and often not until a few hours. A listed breaker is expected to trip in several seconds to 3 minutes for a 3,600 watt continuous load.
Take all those numbers and go up by 33% for a house or apartment with 20A circuits (quite common). Go up by 667% for an oven plug.
As anyone who takes care of rentals during winter knows, a typical circuit can tolerate two 1,500 W space heaters without tripping very much (although this is unsafe and a bad idea).