Comment by bluGill

1 day ago

The biggest problem with plugging a generator into an outlet is you need a double ended cord. If you use everything correctly they work fine, but there are too many ways things can go wrong. The most obvious one is you plug everything in, start the generator, and the trip over the cord on you way back inside, thus sending the live male end flying toward you. Once in a while a kid will see these dual male plugs and plug them in - lots of ways things can go wrong here.

There is also the problem of backfeeding, but this is more theoretical - even if you know to limit your power use, your neighbors won't and so your generator will trip its own breaker. Linemen are taught to either treat power lines like they are live, or to short them to ground - it can happen they don't do this and you kill a linemen, but still not as big a worry as it is made out.

They make generator "inlets" that sidestep all these problems when used correctly. Most common I've seen is a block so you can't have the inlet and the main breaker both on at once.

> There is also the problem of backfeeding, but this is more theoretical

it is not theoretical from the POV of power company employees working on their lines. the power goes out, they go to fix the equipment or wiring, and if the inverters connected to the grid have not shutdown, there could be 10s of kW to even MWs being backfed into the system they are working on.

that's why in the US at least, grid-tied inverters are required to have protection against this. if they do not see power from the grid, they shutdown (and rather quickly).

  • Hang on. You didn't address the reason they gave in the half sentence your quote skipped. How are those backfeeders going to keep going when there's way way more load than they can possibly supply?

  • > if they do not see power from the grid, they shutdown

    I realize this is a complete noob question but I'm still curious: with enough "backfeeders" could it not in theory be possible that the backeeders see each other's output and keep operating?

    Say, a few houses at the end of the line, each with very little electricity consumption (no-one's at home), but with panels and inverters going full tilt, something like that?

    • Yes, this is a concern with some older inverter designs. They use phase-locked loops which are meant to lock to the grid frequency but if you and your neighbours on the feeder are generating and consuming a roughly equal amount of energy and the feeder loses its connection to the wider grid, the loops can lock to each other and form a stable island. How long this would last in practice is not really known, it would probably be rare for it to happen at all and even rarer to stay stable for more than a few minutes but it has been demonstrated so it could have become an issue. Newer inverter have specific anti-islanding protection to detect situations like this and disconnect if it happens.

      (the specific case of very little consumption but panels and inverters going full tilt doesn't work as this would lead to the frequency rapidly increasing, exceeding inverter set points and the local grid collapsing with all the inverter tripping off. The danger scenario is closely matched load and generation, like a real grid)

      1 reply →

    • Apparently the anti-islanding features in the inverters prevent this kind of situation. They need several minutes of clean power to start back up, and do other checks.

  • Again, all linemen are taught to short the wires or they are alive. All grids have regular places where two different lines meet and there is a switch at those points where in the worst case is they can cut the down line close a switch that normally is open and they can back feed a line from a different one and get power to people who are on each side of the break and then they can come back later to fix the break. These switches are miles apart, which means that you cannot be sure while you're working on the line someone else didn't go to that switch and change it.

    Also, people have been back peeking the grid from their home generators for decades by now. Solar and inverters are a different variation of that attack, but it is nothing new. Any utility will have procedures because they can't guarantee that's not happening and we learned years ago.

    I'm not saying it never happens, only that correct procedure already makes it not an issue

  • Yep, and they see the power by trying to increase/decrease the frequency of their own output and sensing the resistance from the grid.